The IFP-2100 (red) and IFP-2100B (black) are intelligent analog/
addressable Fire Alarm Control Panels (FACP). The basic IFP-2100 panel
contains one built in signaling line circuit (SLC), which can support 159
System Sensor® IDP/SK sensors and 159 IDP/SK modules or 127 Hochiki®
SD devices per loop. Additional SLC loops can be added using the model
6815 SLC expander for IDP/SK devices to increase the overall point capacity
to 2100 or model 5815XL for SD devices to increase the overall point
capacity to a maximum to 2032 points per panel.
IFP-2100 has the interconnection capability for up to 32 panels. The system
has two modes of operation, multiple panels covering one larger building, or
multiple independent buildings. The RFP-2100 (red) or RFP-2100B (black)
can be used in a networked system where at least one IFP-2100 is in the
system. It is the same as the IFP-2100 without the display.
IFP-2100 has eight on-board Flexput™ circuits that can be configured for
auxiliary power, notification outputs, or for conventional smoke detector
inputs (Class A or Class B). The FACP also has a Built in dual phone line
digital alarm communicator/transmitter (DACT), IP or optional cellular
technologies, Form C trouble relay, and two programmable Form C relays.
IFP-2100 has powerful features such as detector sensitivity, day/night
thresholds, drift compensation, pre-trouble maintenance alert, and
calibration trouble alert
IFP-2100 / RFP-2100 Technical Specifications
PHYSICAL
Overall Dimensions: 26.4”H x 16.4″W x 4.11”D
Shipping Weight: 33 lbs.
Color: Red or Black
ENVIRONMENTAL
Operating Temperature: 32°F to 120°F (0°C to
49°C)
Humidity: 0 to 93% relative humidity (noncondensing)
ELECTRICAL
IFP-2100 Primary AC: 120VAC @ 50/60Hz, 4.5A
IFP-2100HV AC: 240VAC @ 50/60Hz, 2.8A
Total Accessory Load: 9A @ 24VDC power-limited
Standby Current: 230mA
Alarm Current: 415mA
Battery Charging Capacity: 17 to 55AH
Battery Size: 18AH max. allowed in control panel
cabinet. Larger capacity batteries can be housed in
RBB accessory cabinet.
Six Conductor Wiring: Two voice bus & four SBUS
FLEXPUT CIRCUITS
Eight circuits that can be programmed
individually as:
Notification Circuits: 3A per circuit @ 24VDC,
power limited
Auxiliary Power Circuits: 3A per circuit @ 24VDC,
power limited.
Initiation Circuit: 100mA per circuit @ 24VDC,
power-limited
AGENCY LISTINGS AND APPROVALS
NFPA 13, NFPA 15, NFPA 16, NFPA 70, & NFPA
72: Central Station; Remote Signalling; Local
Protective Signalling Systems; Auxiliary Protected
Premises Unit; & Water Deluge Releasing Service
UL Listing
CSFM 7165-0559:0505
FDNY COA# 6251
Seismic (CA) (pending)
FM approved
APPROVED RELEASING SOLENOIDS
Asco T8210A107 24 VDC 3 A max 0 Hz
Asco 8210G207 24 VDC 3 A max 0 Hz
COMPATIBLE DEVICES
See the data sheets listed below for a complete
listing of the IDP, SK, SWIFT or SD devices.
3350361: IDP Device Protocol data sheet
53623: SK Device Protocol data sheet
350360: SD Device Protocol data sheet
350615 & 350617: SWIFT devices data sheet
ORDERING INFORMATION
IFP-2100: Intelligent Fire Alarm Control Panel. Red
Cabinet.
IFP-2100B: Intelligent Fire Alarm Control Panel.
Black Cabinet.
IFP-2100HV: High Voltage (240V) Intelligent Fire
Alarm Control Panel. Red Cabinet
IFP-2100HVB: High Voltage (240V) Intelligent Fire
Alarm Control Panel. Black Cabinet
RFP-2100: Remote Fire Alarm Panel without built
in display. Red Cabinet.
RFP-2100B: Remote Fire Alarm Panel without built
in display. Black Cabinet.
RFP-2100HV: High Voltage (240V) Remote Fire
Alarm Panel without built in display. Red Cabinet.
RFP-2100HVB: High Voltage (240V) Remote Fire
Alarm Panel without built in display. Black Cabinet.
SBUS ACCESSORIES
RA-2000, RA-1000, RA-1000R, RA-100,
RA-2000GRAY: Remote annunciators
6815: Signal Line Circuit (SLC) Expander for IDP or
SK devices
5815XL: Signal Line Circuit (SLC) Expander for SD
devices
RPS-1000/B: Power Supply. Red or Black Cabinet
5496: NAC Expander
5824: Serial/Parallel Module
5880: LED I/O Module
5865-3 or 5865-4: LED Annunciator
5883: Relay Interface
MISCELLANEOUS ACCESSORIES
HFSS: Software Suite. Provides programming,
upload/download and event reporting
RBB: Remote Battery Box Cabinet. Use for backup
batteries up to 35AH. Dimensions: 16″W x 10″H x
6″D
SK-SCK: Seismic Compliance Kit
SK-NIC: Network Interface Card
SK-FML: Multi Mode Fiber Card
SK-FSL: Single Mode Fiber Card
CELL-MOD: Cellular Communicator in Plastic
Enclosure
CELL-CAB-SK: Cellular Communicator in Metal
Enclosure with lock and key











There are no reviews yet.